| Analogue inputs |
Depending upon the device two or three 0 to 10 V inputs
are available.
The resolution is 10 Bit = 0 to 1 023.
Valid:
 |
| |
Caution!
Analogue signals are more sensitive to interference than digital
signals, therefore the signal cables should be carefully routed and
connected. Inappropriate connections can lead to unwanted switching
conditions.
- Use screened, twisted pair conductors, to stop interference of
the analogue signals.
- With short conductor lengths earth the screen on both sides and
fully. With a conductor length of approx. 30 m the earthing on both
sides can lead to circulating currents between the earthing points
and interference of the analogue signals. In this case only earth
the conductor on one side.
- Don't lay the signal conductor parallel to the power conductor.
- Inductive loads that must be switched by easy should be
connected to a separate power supply or a suppressor circuit should
be used for motors and valves. Supplying loads such as motors,
magnetic valves or contactors and easy from the same power supply
can by switching lead to interference of the analogue input signal.
|
| |
| |
| |
|