All about Motors Star-delta switching of three-phase motors |
| |
| Automatic reversing star-delta starter SDAIUL |
| Reversing |
 |
Rating of switchgear
Q11, Q12 = Ie
F2, Q15 = 0.58 × Ie
Q13 = 0.33 × Ie
The maximum motor output is limited by the upstream reversing contactor,
and is lower than with automatic star-delta starters for only one
direction of operation
Standard version: relay current = motor rated current × 0.58
Reversing after actuation of pushbutton 0
|
 |
Method of operation
Pushbutton I energizes contactor Q11 (e.g. clockwise), pushbutton II
energizes contactor Q12 (e.g. anticlockwise). The contactor first
energized applies voltage to the motor winding and maintains itself via
its own auxiliary contact 14–13 and pushbutton 0. The normally open
contact 44–43 fitted to each mains contactor energizes the star
contactor Q13. Q13 energizes and switches on motor M1 in the star
connection. At the same time, timing relay K1 starts. When the set
changeover time has elapsed, K1/17–18 opens the circuit of Q13. Q13
drops out. K1/17–28 closes the circuit of delta contactor Q15.
Delta contactor Q15 energizes and switches motor M1 to the delta
configuration, i.e. full mains voltage. At the same time, normally
closed contact Q15/22–21 interrupts the circuit of Q13, thus
interlocking against renewed switching on while the motor is running.
Motor direction can be changed, either after pressing pushbutton 0, or
by direct actuation of the reverse button, depending upon the circuit.
In the event of an overload, disconnection is effected by the normally
closed contact 95–96 of the overload relay F2.
|
|