| Contactor for capacitor DIL…K – Individual and group compensation |
Group compensation

Additional inductance with standard contactor |
In the case of group compensation where capacitors are connected in parallel, it must be noted that the charging current is
taken not only from the mains but also from the capacitors connected in parallel. This produces inrush current peaks which can exceed 150 times
the rated current. A further reason for these peak currents is the use of low-loss capacitors as well as the compact construction, with short
connecting elements between contactor and capacitor.
Where standard contactors are used, there is danger of welding. Special
contactors for capacitors such as those available from Moeller in the DILMK… range, which can control inrush current peaks of up to 180 times
the rated current, should be used here.
If no special contactors are available, the inrush currents can be
damped by additional inductance's. This is achieved either by longer incoming leads to the capacitors or by inserting an air-cored coil with
a minimum inductance of approximately 6 µH (5 windings, diameter of the coil approximately 14 cm) between contactor and capacitor. The use of
series resistors is another way of reducing high inrush currents. |
| Use of reactors |
| Frequently the capacitors in group compensation are provided with reactors to avoid harmonics. The reactors also act to
limit the inrush current and normal contactor can be used. |
|