Connection examples, DM4
 
Delta connection
 
A delta connection allows the use of a soft starter with a lower rating than the motor it is used to control. Connected in series with each motor winding, the current the soft starter needs to supply is reduced by a factor of √3. This layout has the drawback that six motor supply cables are needed. Apart from that there are no restrictions. All soft starter functions remain available.

For this you have to connect the motor in delta and the voltage in this connection method must agree with the mains voltage. For 400 V mains voltage the motor must therefore be marked with 400 V/690 V.
Control section
klockner moeller delta connection
  Emergency-Stop
S1: Off
S2: On

Position 1 Enable
Position 2 Soft start/Soft stop
E2: Enable
T1: +thermistor
T2: –thermistor

DM4-340 Delta
klockner moeller delta connection
Position 1 Control voltage through Q1 or F1 or through Q2
Position 2 See Control section
Position 3 Motor current indication



 