All about Motors Multi speed switch for three-phase motors |
| |
| 2 separate windings, non-reversing, 2 speeds |
| |
| Multi-speed contactor UPDIUL, with fuses and overload relay |
 |
Circuit A 1 three-way pushbutton |
Circuit C 1 three-way pushbutton |
 |
 |
Q17: Mains contactor, low speed Q21: Mains contactor, high speed

Three-way pushbutton I: Low speed (Q17) 0: Stop II: High speed (Q21 + Q23) |
 |
Method of operation Actuation of pushbutton I energizes the coil of contactor Q17. Q17
brings in the motor at low speed, and after pushbutton I is released, maintains itself via its auxiliary contact 13–14 and pushbutton 0.
Speed can be changed either after pressing pushbutton 0, or directly by pressing the appropriate pushbutton, depending upon the circuit. The
motor is switched off either by pressing pushbutton 0, or in the event of an overload, by normally closed contact 95–96 of overload relays F2
and F21.
|
|