Klockner Moeller Electric Parts from KlocknerMoeller.net

Klockner Moeller Electric Parts Experts

Call Toll Free!  

1-877-595-9616

Moeller Electric Live Chat

Largest Authorized Stocking USA Distributor  Representing

Moeller Electric LOGO --- Formally Klockner Moeller  German Made Quality Available from US owned company! 1-866-595-9616

 
All about Motors
Motor protection
 
Motor protection in special applications
 
Heavy starting duty
An adequate tripping delay is essential in order to allow a motor to start up smoothly. In the majority of cases, overload relays ZB, motor-protective circuit-breakers PKZ(M) or circuit-breakers NZM can be used. The tripping delays can be taken from the tripping characteristics in the Moeller Main Catalogue, Industrial Switchgear.

In the case of especially high-inertia motors, whose run-up time exceeds the tripping delay of the above devices, it would be completely wrong to adjust an overload relay which tripped out before the run-up time expired, to a current level higher than the rated motor current. This would, it is true, solve the starting problem, but the motor would no longer be adequately protected during normal operation. However, there are other solutions to the problem:
Current transformer-operated relay ZW7
The ZW7 consists of three special saturable core current transformers, supplying an overload relay Z00. It is used principally for medium and large motors.

Up to two times rated current Ie, the transformation ratio I1/I2 of the saturable core current transformers is practically linear. Within this range it does not differ from the normal overload relay, i.e. it provides normal overload protection during normal operation. However, within the transformer characteristic range (I > 2 × Ie) , the secondary current no longer increases proportionally to the primary current.

This non-linear increase in the secondary current produces an extended tripping delay if overcurrents greater than twice rated current occur, and hence permits longer starting times.

 
Adjusting the current transformer-operated relay ZW7 for lower motor ratings
The setting ranges quoted in the Moeller Main Catalogue, Industrial Switchgear apply when the incoming cable is looped once through the transformer relay.

If the current transformer-operated overload relay ZW7 is required to provide protection to a motor of below 42 A rating (minimum value in the setting range of 42 A to 63 A), the necessary range adjustment is achieved by looping the incomer several times through the aperture in the relay. The change in the rated motor current quoted on the rating plate is inversely proportional to the number of loops.

Example: [t-head3]
With the ZW7-63 relay, which has a setting range from 42 A to 63 A, a motor rating of 21 A to 31.5 A can be accommodated by looping the leads twice through the relay.

 



 

Hit Counter