Klockner Moeller Electric Parts from KlocknerMoeller.net

Klockner Moeller Electric Parts Experts

Call Toll Free!  

1-877-595-9616

Moeller Electric Live Chat

Largest Authorized Stocking USA Distributor  Representing

Moeller Electric LOGO --- Formally Klockner Moeller  German Made Quality Available from US owned company! 1-866-595-9616

 
Contactors and Relays
Control relay easy, Multi Function Display MFD-Titan®
 
Network connection
 
Sockets RJ 45 and plug
Connection layout of socket RJ 45 on easy and MFD-Titan.
Klockner Moeller Network Connection
Connection layout of plug RJ45 on easy and MFD-Titan.
Cable entry side
8 pole RJ 45, EASY-NT-RJ 45
Layout with EASY-NET
PIN 1; ECAN_H; Data conductor; conductor pair A
PIN 2; ECAN_L; Data conductor; conductor pair A
PIN 3; GND; ground conductor; conductor pair B
PIN 4; SEL_IN; Select conductor; conductor pair B
Configuration of the network cable for EASY-NET
The network cable does not need to be screened.
The characteristic impedance of the cable must be 120 Ω.


Note
The minimal operation with easy-NET functions with the conductors ECAN_H, ECAN_L, GND. The SEL_IN conductor is solely for automatic addressing.
Bus terminal resistor

A bus terminal resistor must be connected to the geographical first and last device in the network:

  • Value of the bus terminal resistor 124 Ω,
  • Connect to PIN 1 and PIN 2 of the RJ-45 plug,
  • Connection plug : EASY-NT-R.
Pre-finished conductors, RJ45 plug on both ends

Hit Counter