Motor-protective circuit-breaker PKZ2 – overview |
| |
| Special motor-protective trip
block ZMR-...-PKZ2 |
| |
This trip block features an overload relay function
which allows the following interesting application:
In the event of an overload, the circuit-breaker does not trip. Instead,
a normally closed contact (95-96) is actuated which switches off the
contactor in the control circuit (contactors up to 18.5 kW, AC-3). At
the same time, a normally open contact (97-98) is actuated, which
ensures remote indication. The normally closed contact and normally open
contact are suitable for carrying two different potentials.
The trip block has a manual and an automatic position:
|
- Automatic position: The normally closed contact and normally
open contact automatically return to the original position after the
bimetallic strips have cooled down. The contact can be actuated
again by actuation, for example, of a pushbutton.
- Manual position: An acknowledgement locally, at the unit, moves
the contacts back to the original position after tripping.
|
| |
| |
|