Electronic motor starters and drives
Rapid Link system
Speed Control Unit RA-SP
Speed control unit RA-SP is used for electronic variable speed control of three-phase motors.

Note:  Unlike the other Rapid Link system devices, the RA-SP speed control unit’s enclosure is fitted with a heat sink and requires an EMC-conformant mounting and connection.
Connections
Speed control unit RA-SP is supplied ready for connection. The connection to the AS-Interface® data bus and the motor is described below. The connection to the power bus is described in the earlier general section “Rapid Link system”.
Klockner Moeller Speed Control
The unit is connected to AS-Interface® through an M12 plug with the following PIN assignment:
Klockner Moeller Speed Control
On the RA-SP the motor feeder features a metal-encapsulated socket. To meet EMC requirements, this is connected with PE and heat sink over a large area. The matching plug is also metal-encapsulated and the motor cable is screened. The length of the motor cable is limited to 10 m. The motor cable’s screen must have a large-area connection with PE at both ends, and the motor connection terminals must also, therefore, meet EMC requirements.

The motor is connected through a halogen-free 4 × 1.5 mm² + 2 × (2 × 0.75 mm²), screened, DESINA-conformant motor supply cable with a length of 2 m, (SET-M4/2-HF) or 5 m, (SET-M4/5-HF).

Alternatively you can assemble your own motor supply cable with plug SET-M4-A, with 4 × 1.5 mm² + 4 × 0.75 mm² contact.
Klockner Moeller Speed Control
Klockner Moeller Speed Control
For controlling braking motors, their manufacturers provide braking rectifiers, which are fitted in the motor terminal strip.

Note:  When using speed control unit RA-SP, do not connect the braking rectifier directly to the motor terminals (U/V/W)