Klockner Moeller Electric Parts from KlocknerMoeller.net
|
 |
Call Toll Free!
1-877-595-9616

|
|
Largest Authorized Stocking USA Distributor
Representing

|
| |
Automation Systems Engineering XC100/XC200 |
| |
| Wiring example of power supply unit |
| |
The voltage terminal 0VQ/24VQ is only used for the
power supply of the local 8 inputs and 6 outputs, and is potentially
isolated from the bus.
The outputs 0 to 3 can be loaded with 500 mA and the outputs 4 and 5
with 1 A, each with a 100 % duty factor (DF) and a simultaneity factor
of 1.
The wiring example shows the wiring with a separate power supply for the
PLC and the IO terminals. If only one power supply is used, the
following terminals must be connected:
24 V to 24VQ and 0 V to 0VQ. |
| |
 |
| |
|